Pt100 / Pt1000 RTD calculator

Convert between temperature and RTD resistance using the standard IEC 60751 curve, for checking a sensor with a multimeter or validating a transmitter.

Resistance
Sensitivity at this point
R0 (at 0 °C)
TemperaturePt100Pt1000

How it works

Platinum RTDs follow the Callendar–Van Dusen equation defined in IEC 60751, with R0 the resistance at 0 °C (100 Ω for a Pt100, 1000 Ω for a Pt1000).

R(T) = R0 [1 + A·T + B·T² + C·(T − 100)·T³]